CASE4GS Power flow data for 4 bus, 2 gen case from Grainger & Stevenson. Please see CASEFORMAT for details on the case file format. This is the 4 bus example from pp. 337-338 of "Power System Analysis", by John Grainger, Jr., William Stevenson, McGraw-Hill, 1994.
0001 function mpc = case4gs 0002 %CASE4GS Power flow data for 4 bus, 2 gen case from Grainger & Stevenson. 0003 % Please see CASEFORMAT for details on the case file format. 0004 % 0005 % This is the 4 bus example from pp. 337-338 of "Power System Analysis", 0006 % by John Grainger, Jr., William Stevenson, McGraw-Hill, 1994. 0007 0008 % MATPOWER 0009 % $Id: case4gs.m,v 1.4 2010/03/10 18:08:14 ray Exp $ 0010 0011 %% MATPOWER Case Format : Version 2 0012 mpc.version = '2'; 0013 0014 %%----- Power Flow Data -----%% 0015 %% system MVA base 0016 mpc.baseMVA = 100; 0017 0018 %% bus data 0019 % bus_i type Pd Qd Gs Bs area Vm Va baseKV zone Vmax Vmin 0020 mpc.bus = [ 0021 1 3 50 30.99 0 0 1 1 0 230 1 1.1 0.9; 0022 2 1 170 105.35 0 0 1 1 0 230 1 1.1 0.9; 0023 3 1 200 123.94 0 0 1 1 0 230 1 1.1 0.9; 0024 4 2 80 49.58 0 0 1 1 0 230 1 1.1 0.9; 0025 ]; 0026 0027 %% generator data 0028 % bus Pg Qg Qmax Qmin Vg mBase status Pmax Pmin Pc1 Pc2 Qc1min Qc1max Qc2min Qc2max ramp_agc ramp_10 ramp_30 ramp_q apf 0029 mpc.gen = [ 0030 4 318 0 100 -100 1.02 100 1 318 0 0 0 0 0 0 0 0 0 0 0 0; 0031 1 0 0 100 -100 1 100 1 0 0 0 0 0 0 0 0 0 0 0 0 0; 0032 ]; 0033 0034 %% branch data 0035 % fbus tbus r x b rateA rateB rateC ratio angle status angmin angmax 0036 mpc.branch = [ 0037 1 2 0.01008 0.0504 0.1025 250 250 250 0 0 1 -360 360; 0038 1 3 0.00744 0.0372 0.0775 250 250 250 0 0 1 -360 360; 0039 2 4 0.00744 0.0372 0.0775 250 250 250 0 0 1 -360 360; 0040 3 4 0.01272 0.0636 0.1275 250 250 250 0 0 1 -360 360; 0041 ];